109

A.6.3 Setup Sensor

For details on this feature, see 9.5 - Setup System - Setup Sensor.

Setup Sensor

SETUP SENSOR

Setup for analog

input points

Select sensor to edit

SENSOR VALUE

1=SENSOR_1 80.0 DEG
2=SENSOR_2 ------ DEG
3=SENSOR_3 80.0 DEG
4=SENSOR_4 79.5 RH
5=RETURN TO SETUP MENU
6=RETURN TO MAIN MENU

SELECT A NUMBER:1

>IS THE SENSOR CONNECTED-YES(Y) OR NO(N)?
>[N]
>[
>COMMAND SUCCESSFUL

>CHANGE SENSOR LABEL(8 CHARACTERS MAX).
>[SENSOR_1]
>[
>COMMAND SUCCESSFUL

>CHANGE UNITS LABEL(3 CHARACTERS MAX).
>[DEG]
>[
>COMMAND SUCCESSFUL

>CHANGE 4 mA VALUE(-999.9 to 999.9).
>[-020.0]
>[
>COMMAND SUCCESSFUL

>CHANGE 20 mA VALUE(-999.9 to 999.9).
>[+020.0]