2 surface-mounting the universal monitor, Required tools, 1 mounting the panel – Liebert Universal Monitor User Manual

Page 19: Figure 5 mounting dimensions, Surface-mounting the universal monitor, Mounting the panel, Figure 5, Mounting dimensions, Caution

Advertising
background image

Installation - Main Board

11

2.2

Surface-Mounting the Universal Monitor

After determining where to place the unit, check to ensure that you have all the hardware required to

install the panel on the surface of a wall. Obtain the needed tools and material.

Required tools

• Electric drill (if surface is too hard to drive screws without pilot holes)
• Screwdriver
• Marker to denote layout of holes
• Four screws, each #10

2.2.1 Mounting the Panel

1. Mark the wall for mounting holes, using the back of the unit as a template (see Figure 5).
2. Drill holes, if required, to install the four #10 screws that will secure the Universal Monitor to the

wall. Clean up the debris.

3. If the wall material is not strong enough to hold the screws securely, use wall anchors.
4. Install the top two screws—the screw heads must be small enough to slip through the larger,

bottom portion of the pear-shaped mounting slot in the Universal Monitor (see inset in Figure 5).

The screws must also be large enough to extend over the edges of the top of the mounting slot.

5. Hang the Universal Monitor on the screws, letting the panel slip down until the screws are in the

smaller, upper portion of the slot.

6. Tighten the screws until they are snug.
7. Insert the remaining two screws in the bottom holes on the back of the panel and tighten.

Figure 5

Mounting Dimensions

NOTE
Removing the conduit knockouts before mounting the Universal Monitor on the wall will ease

installation and prevent strain on the mounting hardware and wall. It is imperative to remove

the knockouts if the unit is to be flush-mounted.

!

CAUTION

Check building plans and other relevant documents to determine whether mounting the

Universal Monitor at the selected location might cause cutting or otherwise damaging

electrical or communication wiring or pipes.

SMALL ENCLOSURE

0.213"

(5.4mm)

Mounting Slot

0.375"

(9.6mm)

Universal Monitor

back plate

12.5"

(317.5mm)

0.213" (5.4mm)

Bottom hole diameter

10"

(254mm)

LARGE ENCLOSURE

0.213"

(5.4mm)

Mounting Slot

0.375"

(9.6mm)

Universal Monitor

back plate

12"

(304.8mm)

0.213" (5.4mm)

Bottom hole diameter

16"

(406.4mm)

Advertising