6 setup serv ph num - enter phone number, Table 32 service phone number dialing results, Setup serv ph num - enter phone number – Liebert Universal Monitor User Manual

Page 82: Table 32, Service phone number dialing results, Table 33, Guidelines for dialing service phone number, Setup serv ph num - enter, Phone number

Advertising
background image

System and Control Options

74

9.9.6 Setup Serv Ph Num - Enter Phone Number

The Service Phone Number (Serv Ph Num) is used for remote monitoring by Liebert Global Services.

The number is designed to allow remote monitoring services to connect to the Universal Monitor. All

alarms will be sent to this number. When an alarm occurs, this number is dialed before any of the

four pager numbers.
To use the service phone number features, be sure to connect the phone line connector to a telephone

wall jack using an RJ11 cord, as described in 4.6.2 - Phone Line Connector.

To set up the service phone number:

• From the Setup System Info Menu, use the arrows

↑ ↓

to

choose

Setup Serv Ph Num, then press Enter ↵ .

• See Table 33 for guidelines on entering the phone number, which

may consist of up to 40 characters. To enter the phone number:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.

Table 32

Service phone number dialing results

Result of Dialing

Action

Message Generated

Successful

Unsuccessful due to:

Busy signal / no answer /

no dial tone

Universal Monitor generates message after all three

redial attempts have failed, dials next configured pager.

Unsuccessful Page

(Event Log)

General modem

communication problem

Universal Monitor resets modem, generates

message, redials up to three more times.

Modem Reset

(Event Log)

No communication with modem

(internal hardware problem)

Universal Monitor generates messages, makes no

further dialing attempts.

Modem Internal Fault

(Active Alarm Report,

Alarm History Log)

Table 33

Guidelines for dialing service phone number

Device type

Required entries

Example

Remote

modem

The first character must be “M”.

M18005551212

Device type

Optional entries

Example

All types

of devices

Use “9” if needed to access an outside

line—place after first character (M).

M918005551212

Use "W" to wait for a second dial tone

before dialing if the phone system has

two dial tones (initial tone and a second

tone for outside line)—place after “9”

(before the number to be dialed).

M9W18005551212

Use “,” (comma) to pause two seconds.

M1,8005551212

Setup System Info Menu

SETUP SYSTEM INFO

CHANGE PASSWORD
CHANGE DATE & TIME

↑ ↓=NEXT

=SELECT

SETUP SITE ID
CONNECT BATTERY

> SETUP SERV PH NUM

FACTORY DEFAULTS

Setup Serv Ph Num

ENTER PHONE NUMBER

M18005551212

↑ ↓=SELECT

=NEXT/END

Advertising