Introduction

6

1.8

Optional Expansion Board Overview

The Universal Monitor Expansion Board, purchased separately, has connectors for 16 digital inputs

and eight digital outputs, as shown below. The board has light emitting diodes (LEDs) to display the

status of monitored output devices, communications ports for connection to the Universal Monitor,

power connections and other features necessary to monitor and protect your operation.

Table 2

Expansion board components

Item

Description

For more information, see:

A - Digital output

connectors (8)

Each of the eight output connections is a two-state point:

ON/OFF (energized/de-energized).
An example of a field digital output point is a motor starter.

5.0:

Wiring and Connections -

Optional Expansion Board

4.2.2: Connecting Digital Outputs

7.6:

View Output Status

9.7:

Setup System - Setup Output

B - Digital output

fuses (8)

Bussmann GMA-2 or equivalent. 250V 2A Fast Blow fuse.
CAUTION: Fuses must be replaced with equivalent fuses.
NOTE: Two (2) replacement fuses are shipped with

the Expansion Board enclosure.

N/A

C - Digital output

DIP switch

DIP switch used for setting Normally Open / Normally

Closed.

5.2.3: Setting the Digital Output DIP

Switches

9.7.3: Set Expansion Board Output by

DIP Switch

D - Digital output

status LEDs (8)

Each output has an LED to indicate its status: ON/OFF

(energized/de-energized).

1.10: LED Indicators - Optional

Expansion Board

E - Digital input

connectors (16)

Each of the 16 input connections is a two-state point: ON/

OFF (energized/de-energized).
An example of a field digital input point is a leak detector.

5.0:

Wiring and Connections -

Optional Expansion Board

4.2.1: Connecting Digital Inputs

7.5:

View Input Status

9.3:

Setup System - Setup Input

F - General status

LED (green)

Indicates the operational status of the Expansion Board.

1.10: LED Indicators - Optional

Expansion Board

G - EIA485 status

LEDs (yellow & red)

Two LEDs indicate status of the EIA485 connection:

ON/OFF (energized/de-energized).

1.10: LED Indicators - Optional

Expansion Board

H - EIA485

connector

Connection to the Universal Monitor.

5.3.1: Connect EIA485 Connectors to

Main Board

9.10: Setup Exp Board - Optional

Expansion Board

I - Power status LED

(green)

Indicates the power status of the Expansion Board.

1.10: LED Indicators - Optional

Expansion Board

J - 24VAC power

connector

Power connection for the Expansion Board. Requires

24VAC.

3.4:

Input Power Connections -

Optional Expansion Board

OUT1

K1

V1

V3

V5

V7

V9

V11

V13

V15

V2

V4

V6

V8

V10

V12

V14

V16

K2

K3

K4

K5

K6

K7

K8

OUT2

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

S4

S3

S2

S1

Multiflex 168AO

810-3065

DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR

USE COPPER (CU) CONDUCTORS ONLY.

D6

POWER INPUT

EIA485 + (to UM-)

0V

EIA485 - (to UM+)

RELAY OUTPUTS

H - EIA485

connector

E - Digital input

connectors (16)

F - General

status LED

(green)

G - EIA485

status LEDs

(yellow & red)

I - Power status

LED (green)

B - Digital

output

fuses (8)

J - 24VAC

power

connector

A - Digital output

connectors (8)

C - Digital

output

DIP switch

D - Digital output

status LEDs (8)