Troubleshooting - transformer module, 3 connecting the battery pack, Obtaining a replacement battery pack – Liebert Universal Monitor User Manual

Page 23: Connecting the battery pack, Warning, Caution

Advertising
background image

Installation - Main Board

15

Troubleshooting - Transformer Module

A common problem and possible solution are shown in the table below. For further information or if

you have other problems with the unit, consult your local dealer, Liebert representative or the Liebert

Worldwide Support Group.

2.4.3 Connecting the Battery Pack

After connecting AC power to the Universal

Monitor, you may connect the panel’s backup

battery (factory-supplied) to the jumpers so it

will begin charging when electrical power to

the Universal Monitor is switched on.

To connect the battery pack, insert the battery

leads into the jumpers as shown at right. (To

disconnect the battery pack, remove the bat-

tery leads from the jumpers.)

Obtaining a Replacement Battery Pack

To obtain a replacement battery pack, contact

your local dealer or Liebert representative.

The Liebert part number is 133455P1.

Problem

Possible Solution

Replacement Fuse Part Numbers

24VAC power

not available

from TB1 or TB2

Check fuse for respective

output (TB1 or TB2).

• LITTLEFUSE 218002

or

• BUSSMANN GDC-2A

NOTE
If the battery is not hooked up before

the Universal Monitor is switched on,

it will trigger an alarm.

!

WARNING

To prevent the risk of fire or explosion,

replace only with 7.2 V rechargeable

NiCad battery pack.

!

CAUTION

Dispose of the battery properly by

sending it back to Liebert Corporation

or an approved battery recycling

facility.

Battery pack connector

Battery pack

Advertising