System and Control Options

49

9.5

Setup System - Setup Sensor

The Universal Monitor has four analog sensor input points that may be configured individually. The

panel monitors connected equipment for any 4-20 mA input—for example, temperature and humidity.
To configure a sensor:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑ ↓

to

choose System and

Control, then press Enter ↵ (see 9.1 - Login for help).

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑ ↓

to

choose

Setup System, then press Enter ↵ .

Select a Sensor to Configure

• From the Setup System Menu, shown at right, use the arrows

↑ ↓

to

choose Setup Sensor and press Enter ↵ .

• From the Select Sensor Menu, choose the sensor you want—for

example, Sensor_1—and press Enter ↵ .

Table 22 shows sensor features that may be changed, along with the

default settings. By default, sensor inputs are not connected.
To activate a sensor input, you must specify it as connected and enter

corresponding values for 4 and 20 mA, as well as high and low set-

points. Other features that may be altered include the name of the sensor, the abbreviation for the

units, and defining the sensor as alarmable or as an event.

• Alarmable sensors may be Latched (Y) or Unlatched (N).
• Event status allows you to monitor a sensor’s high and low setpoints—and use those setpoints to

change the status of an output, if desired—without triggering an alarm. Events are always

Unlatched.

• You may also specify a time delay before the Universal Monitor responds to an alarm or event.

Use the steps following Table 22 to change the default settings for any analog sensor input.
Table 22

Default settings - analog sensor inputs

Feature

Default

Other Options

CONNECTED*

N (Not connected)*

Y (Connected)**

LABEL

SENSOR_1

Any name (up to eight characters)

UNITS

Blank

Any units (up to three characters)

4 mA

-999.9

Can define up to two decimal places—for example, -99.99

20 mA

+999.9

Can define up to two decimal places—for example, +99.99

OFFSET

+000.0

Can define up to two decimal places—for example, +00.00

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

N (Unlatched)

Y (Latched)

LOW SETPT

-0999.9

Can define up to two decimal places—for example, -999.99

HIGH SETPT

+0999.9

Can define up to two decimal places—for example, +999.99

SENSOR DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* If a sensor is configured as N (Not connected), the display will show an empty reading (blank spaces).
** If a sensor is configured as Y (Connected) and is functioning properly, the display will show a reading. If the

connected sensor is not functioning properly, the display will show dashes (------) indicating a problem.

Setup System Menu

SETUP INPUT
SETUP COMMON ALARM

> SETUP SENSOR

SETUP I/O MATRIX

↑ ↓=NEXT

=SELECT

SETUP OUTPUT
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP EXP BOARD

Select Sensor Menu

SELECT SENSOR

> SENSOR_1 +80.00 DEG

SENSOR_2 ------ DEG

↑ ↓=NEXT

=SELECT

SENSOR_3
SENSOR_4 +79.50 RH