System and Control Options

54

9.5.11 Set Up Delay Time

Each sensor may be set up with a specified time delay between the

triggering of a high or low setpoint—a monitored sensor crosses the

high or low setpoint threshold—and any response by the Universal

Monitor. This feature can prevent transient conditions from prompting

unnecessary responses.
This delay is the amount of time that must elapse before the Universal

Monitor acknowledges the change in the monitored sensor and takes

any further action, such as dialing configured pagers. The default time

delay is 1 second (displayed as 00 MIN : 01 SEC).
The time delay applies to the triggering of a high or low setpoint and

also after the monitored sensor returns to its normal state. When the

monitored device returns to its normal state, the specified time delay

must elapse before the Universal Monitor acknowledges the return-to-

normal condition.

• From the Setup Sensor Menu, choose Sensor Delay, as shown at

right, and press Enter ↵ .

• To change the time delay in minutes and seconds (in the range of

00:00 to 99:59):

• For minutes (MIN), press and hold one of the arrow keys

↑ ↓

scroll through the numbers

00-99.

• Press Enter ↵ to advance to seconds (SEC).
• For seconds (SEC), press and hold one of the arrow keys

↑ ↓

scroll through the numbers 00-59.

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED : Y
LABEL: ROOM_TMP

↑ ↓=NEXT

=SELECT

UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +055.00
HIGH SETPT: +085.00
SENSOR DELAY: 00:01

Delay Time

DELAY TIME BEFORE
TRIGGER?

00 MIN : 01 SEC

↑ ↓=SELECT

=NEXT/END