Silence Alarm & Backup Log Files (Service Terminal Interface)

42

5. At the top of the HyperTerminal window, shown below, click on Transfer, then on Receive File.

6. In the Receive File window, as shown above:

• In the Place Received File in the Following Folder box, enter the name and location of the

folder where the configuration file should be placed—for example, C:\downloads—or click

on the Browse button to locate the folder.

• In the Use Receiving Protocol box, select Xmodem from the drop-down list.
• Click on the Receive button. (To close the window without backing up the file, click on Close

or Cancel.)

7. In the Receive Filename window, enter a name for the log file—Alarm.log in the example above.
8. When the transfer is complete, a confirmation message appears in the Service Terminal Interface

window: “Backup Successful.”

9. The display returns to the Backup Log Files menu. You may choose another type of log file to back

up (return to Step 3) or press 7 (or Escape) to return to the Main Menu.

After backing up a log file, you may want to delete all records in the Universal Monitor’s log of that

type. See 9.12 - Clear Alarms & Logs for details.