11 manual output ctrl, Manual output ctrl, Table 34 – Liebert Universal Monitor User Manual

Page 88: Automatic / manual control - output points

Advertising
background image

System and Control Options

80

9.11 Manual Output Ctrl

The Manual Output Ctrl feature allows you to manually change the state of any digital output to ON

or OFF, overriding automatic control by the Universal Monitor (the default setting for all outputs).

This menu also allows you to release the manual override, returning any output to automatic control.
There are two ways to override automatic control of outputs:

• Use the Manual Output Ctrl menu, as described in this section, to turn any output ON or OFF.
• Use the switch on the Universal Monitor board (see 1.7 - Controller Board Overview) to force

all eight outputs ON at the same time. (Note: This has no effect on the optional Expansion Board

outputs.)

After an output is forced manually ON or OFF through the Manual Output Ctrl menu, it remains in

that state until returned to automatic control through this menu.
Table 34 summarizes the four types of control, including the abbreviated message that appears on

the LCD and in log reports.

To force an output point ON or OFF or return it to automatic control:

Log In and Choose Manual Output Ctrl

• From the Main Menu, use the arrows

↑ ↓

to

choose System and

Control, then press Enter ↵ (see 9.1 - Login for help).

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑ ↓

to

choose

Manual Output Ctrl, then press Enter ↵ .

Select an Output
The Select Output menu, shown at right, display the current status

of all eight outputs.

• Use the arrows

↑ ↓

to

choose the output you want—for example,

Output01—and press Enter ↵ .

Turn Output ON or OFF / Return to Automatic

• From the Override Output menu, use the arrows

↑ ↓

to

choose

one of these options:

Auto (return to automatic control)
Man ON (manually turn this output ON)
Man OFF (manually turn this output OFF)

• Press Enter ↵ .

Table 34

Automatic / manual control - output points

Message

Description

AUTO

Automatic

Controlled by Universal Monitor

MAN ON

Manually ON

This output forced ON or OFF

via Manual Output Ctrl menu

MAN OFF

Manually OFF

HW MAN ON

Manually ON

(all outputs)

All outputs forced ON

via hardware switch on circuit board

Main Menu

VIEW STATUS

> SYSTEM AND CONTROL

↑ ↓=NEXT

=SELECT

Login

LOGIN

AAAA

↑ ↓=SELECT

=NEXT/END

System & Control Menu

SETUP SYSTEM

> MANUAL OUTPUT CTRL

CLEAR ALARMS & LOGS

↑ ↓=NEXT

=SELECT

Select Output

OVERRIDE OUTPUT

> OUTPUT01

AUTO

OUTPUT02

AUTO

↑ ↓=NEXT

=SELECT

OUTPUT03

AUTO

OUTPUT04

MAN ON

OUTPUT05

AUTO

OUTPUT06

AUTO

OUTPUT07

MAN OFF

OUTPUT08

AUTO

OUTPUT09

AUTO

OUTPUT10

MAN ON

OUTPUT11

AUTO

OUTPUT12

AUTO

OUTPUT13

MAN OFF

OUTPUT14

AUTO

OUTPUT15

AUTO

OUTPUT16

AUTO

Override Output

SELECT OUTPUT01

AUTO

↑ ↓=SELECT

=END

NOTE: OUTPUT09-OUTPUT16

for optional Expansion Board

Advertising