2 connecting inputs and outputs, 1 connecting digital inputs, Connecting inputs and outputs – Liebert Universal Monitor User Manual

Page 34: Connecting digital inputs

Advertising
background image

Wiring and Connections - Optional Expansion Board

26

5.2

Connecting Inputs and Outputs

The Universal Monitor’s optional Expansion Board permits the addition of 16 input and eight output

devices. This section describes how to connect devices to the Expansion Board’s inputs and outputs.
To determine the proper wire size, see Table 9.

5.2.1 Connecting Digital Inputs

The 16 digital inputs are found on the lower portion of the Expansion Board, as shown below. These

inputs are numbered 9 through 24 (the Universal Monitor’s digital inputs are numbered 1 through 8).

To connect an input:
1. Disconnect all electrical power from the Expansion Board.
2. If necessary, remove a conduit knockout to permit wire entry into the Expansion Board enclosure.
3. Bring the wire(s) into the Expansion Board enclosure through a conduit knockout or access slot.
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.
5. Tighten the screw until it holds the wire snugly.

NOTE
Each terminal block is a removable assembly to permit easier connection of more than one

input at a time. If making multiple connections, grasp the upper portion of a block and pull

firmly until the assembly pulls apart.
After making the connections, push the removed piece back into the portion attached to the

printed wiring assembly until the terminal block pieces lock together.

OUT1

K1

V1

V3

V5

V7

V9

V11

V13

V15

K2

K3

K4

K5

K6

K7

K8

OUT2

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

S4

S3

S2

S1

68AO

DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR

EIA485 + (to UM-)

0V

EIA485 - (to UM+)

INPUT TERMINAL BLOCKS

Note numbering keys below terminal blocks;

inputs are numbered from left (9) to right (24)

Numbering keys

Advertising