Introduction

5

K - Digital output loss-

of-power jumper

One of eight output jumpers. Each digital output has a

jumper to set the fail-safe position of the output point when

power fails. The OFF position makes the contact Normally

Open (factory default). The ON position makes the contact

Normally Closed.

Note: The jumper position has no effect on the contact

when the Universal Monitor has power.

4.2.3: Setting the Digital Output

Jumpers

9.7.4: Configure Main Board Output

for Loss of Power (“Fail-

Safe”)

L - Digital input

connectors

Each of the eight input connections is a two-state point:

ON/OFF (energized/de-energized).

An example of a field digital input point is a leak detector.

4.0:

Wiring and Connections -

Main Board

4.2.1: Connecting Digital Inputs

7.5:

View Input Status

9.3:

Setup System - Setup Input

M - Digital input status

LEDs

Each input has an LED to indicate its status: ON/OFF

(energized/de-energized).

1.9:

LED Indicators

N - Analog ground

connector

Connection for an externally powered analog sensor that

needs a reference to ground.

4.3.2: Connecting the Analog

Ground

O - Analog input

connectors

Each of the four input connections accepts a 4/20 mA

signal.

An example of a field analog input point is a temperature

sensor.

4.0:

Wiring and Connections -

Main Board

4.3:

Connecting Analog Inputs

7.5:

View Input Status

9.5:

Setup System - Setup

Sensor

P - 12VDC/24VDC

analog input jumper

One jumper to select voltage supplied for two-wire analog

sensors. The jumper supplies all four analog input

connectors with the same voltage. Factory default is 24VDC.

4.3.1: Setting the 12VDC/24VDC

Analog Power Jumper

Q - SiteScan Web

connector (EIA422)

Connection to monitor Universal Monitor from Liebert’s

SiteScan Web graphical monitoring package.

4.0:

Wiring and Connections -

Main Board

4.5:

EIA422 SiteScan Web

Connector

R - EIA485 connector

Connection to optional Expansion Board (purchased

separately). Connect maximum of one Expansion Board.

4.0:

Wiring and Connections -

Main Board

5.3.1: Connect EIA485 Connectors

to Main Board

S - Serial interface

connector (RS232/

EIA574)

Connection for laptop or video terminal. Used for

configuration and monitoring using the Service Terminal

Interface. Requires a null modem cable for connectivity

(P/N 201258P1).

4.6.1: RS232 Connector

A.2: Connecting to the Service

Terminal Interface

T - Phone line

connector

Connection for phone line. Used for pager notifications,

service phone number, and configuration and monitoring

using the Service Terminal Interface. Requires an RJ11

connector.

4.6.2: Phone Line Connector

9.8:

Setup System - Setup

Modem & Pagers

9.9.6: Setup Serv Ph Num - Enter

Phone Number

A.2: Connecting to the Service

Terminal Interface

U - Power receptacle

(Transformer Module)

115VAC power receptacle to power laptop during

configuration and diagnostics. Receptacle not available on

230VAC Transformer Module.

2.4.2: Termination and Mounting -

Large Enclosure

4.0:

Wiring and Connections -

Main Board

V - Power On/Off

switch (Transformer

Module)

Power switch to turn power On/Off to both Transformer

Module 24VAC connectors and power receptacle.

2.4.2: Termination and Mounting -

Large Enclosure

4.0:

Wiring and Connections -

Main Board

W - 24VAC connector

(Transformer Module)

One of the two 24VAC connectors for power (the second is

also on the right side of the Transformer Module near the

top). Each connector is rated for 40VA.

2.4.2: Termination and Mounting -

Large Enclosure

4.0:

Wiring and Connections -

Main Board

X - Modem

On-board modem with 9600 baud rate.

9.8:

Setup System - Setup

Modem & Pagers

Y - Modem status LEDs

Indicates the operational status of the modem.

1.9:

LED Indicators

Z - DIP switch 1

DIP switch used for resetting password to default.

9.9.1: Change Password

AA - LCD connector

Connection for the LCD on the enclosure door.

N/A

BB - LCD contrast

adjustment

Adjustment contrast for the LCD on the enclosure door.

N/A

CC - Battery pack

connector

Connection for battery pack lead.

2.4.3: Connecting the Battery Pack

DD - 24VAC power

connector

Power connection for the controller. Requires 24VAC.

2.4:

Connect Power to the

Universal Monitor

EE - Transformer

Module

Transformer Module used to convert 115VAC or 230VAC

to 24VAC. Available only in the large enclosure.

2.4.2: Termination and Mounting -

Large Enclosure

Table 1

Controller board components (continued)

Item

Description

For more information, see:

Advertising