9.6.2 Set Up Mapping for an Analog Sensor Input

• Use the arrows

↑ ↓

to

choose Map Sensor To Outpt from the Map

Input/Sensor Menu, and press Enter ↵ .

• From the Select Sensor Menu, choose the input you want—for

example, Sensor_1 High Stpt—and press Enter ↵ .

Map Sensor to Main Board Output

• From the Select Outputs menu, select Map to Main Board if you

want to map the selected sensor to an output on the Universal

Monitor main board. These outputs are identified as Outputs 1-8.

• On the Output Map screen, you may map the selected sensor to any

of the eight outputs (1-8)—or to more than one output, if desired.

The example at right shows Sensor_1 High Stpt mapped to

Output04.
To make changes to the mapping:

• If needed, press Enter ↵ to advance to the position directly

below the output.

• Use the arrows ↑ ↓ to choose Y (Yes - Mapped to this output) or

N (No - Not mapped), then press Enter ↵ .

• Press Enter ↵ to advance to the next position where you want

to make a change.

• Use the arrows ↑ ↓ to choose Y (Yes - Mapped to this output) or

N (No - Not mapped), then press Enter ↵ .

• When finished, press Enter ↵ again.

Map Sensor to Expansion Board Output

• From the Select Outputs menu, select Map to Exp Board if you

want to map the selected sensor to an output on the optional

Expansion Board. These outputs are identified as Outputs 9-16.

• On the Output Map screen, you may map the selected sensor to any

of the eight outputs (9-16)—or to more than one output, if desired.

The example at right shows Sensor_1 High Stpt mapped to

Output11.
To make changes to the mapping:

• If needed, press Enter ↵ to advance to the position directly

below the output.

• Use the arrows ↑ ↓ to choose Y (Yes - Mapped to this output) or

N (No - Not mapped), then press Enter ↵ .

• Press Enter ↵ to advance to the next position where you want

to make a change.

• Use the arrows ↑ ↓ to choose Y (Yes - Mapped to this output) or

N (No - Not mapped), then press Enter ↵ .

• When finished, press Enter ↵ again.

Default Mappings - Analog Inputs to Outputs

By default, analog inputs are not mapped to any digital output, as shown in Table 24.
Table 24

Default mapping of analog inputs to digital outputs

Analog input

By default, mapped to digital output:

Sensor_1

(none)

Sensor_2

(none)

Sensor_3

(none)

Sensor_4

(none)

Map Input/Sensor Menu

MAP INPUT TO OUTPUT

> MAP SENSOR TO OUTPT

↑ ↓=NEXT

=SELECT

Select Sensor

SELECT SENSOR

> SENSOR_1 HIGH STPT

SENSOR_1 LOW

STPT

↑ ↓=NEXT

=SELECT

SENSOR_2 HIGH STPT
SENSOR_2 LOW

STPT

SENSOR_3 HIGH STPT
SENSOR_3 LOW

STPT

SENSOR_4 HIGH STPT
SENSOR_4 LOW

STPT

Select Outputs

SELECT OUTPUTS

> MAP TO MAIN BOARD

MAP TO EXP BOARD

↑ ↓=NEXT

=SELECT

Output Map

1H

OUTPUT MAP

1 2 3 4 5 6 7 8
N N N Y N N N N

↑ ↓=Y/N

=NEXT/END

Select Outputs

SELECT OUTPUTS

MAP TO MAIN BOARD

> MAP TO EXP BOARD

↑ ↓=NEXT

=SELECT

Output Map

1H

OUTPUT MAP

0910111213141516

N N Y N N N N N

↑ ↓=Y/N

=NEXT/END

Advertising