9.4

Setup System - Setup Common Alarm

The audible alarm sounds after the Universal Monitor detects an alarm condition in any input that

has been defined as alarmable, including digital and analog sensor inputs. Once the alarm is silenced,

there are two options:

• By default, the common alarm remains energized until the input alarm is cleared.
• You may change this setting to de-energize the common alarm automatically once the alarm is

silenced.

You might want to reset the common alarm with silence if an external alarm—for example, a horn—is

connected to the common alarm output contacts.
You might not want to reset the common alarm contacts (let contacts reflect/track alarms) and simply

silence the audible horn.
To change the common alarm setting:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑ ↓

to

choose System and

Control, then press Enter ↵ (see 9.1 - Login for help).

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑ ↓

to

choose

Setup System, then press Enter ↵ .

Change to Reset (Y) or Not Reset (N)

• From the Setup System Menu, shown at right, use the arrows

↑ ↓

to

choose Setup Common Alarm and press Enter ↵ .

• By default, the common alarm is set up not to reset automatically

when the alarm is silenced (N). To change this setting, use the

arrows

↑ ↓

to

choose Y (Yes - reset with silence) or N (No - not

reset), then press Enter ↵ .

Setup System Menu

SETUP INPUT

> SETUP COMMON ALARM

SETUP SENSOR
SETUP I/O MATRIX

↑ ↓=NEXT

=SELECT

SETUP OUTPUT
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP EXP BOARD

Reset Common Alarm

RESET COMMON ALARM
WITH SILENCE? N

↑ ↓=Y/N

=END