2 connecting digital outputs, Figure 11 form c output contact wiring, Connecting digital outputs – Liebert Universal Monitor User Manual

Page 35: Warning, Caution

Advertising
background image

Wiring and Connections - Optional Expansion Board

27

5.2.2 Connecting Digital Outputs

The eight digital outputs are found at the top of the Expansion Board, as shown below. These inputs

are numbered 9 through 16. (Note that the digital outputs on the main board of the Universal Monitor

are numbered 1 - 8.)

Each output may be wired according to whether you want the output to be Normally Open or Nor-

mally Closed. The Expansion Board outputs are Form C relay contacts, each with three terminals.

There are two ways to wire the outputs, as shown in Figure 11.

• One wire of the two-wire connection should always be connected to the middle terminal.
• The second wire may be connected to either the N.C. terminal or the N.O. terminal, depending on

how whether you want the contact to be closed or open during a power failure:

• Connect to the N.C. terminal if you want the path to be CLOSED during a power failure, or
• Connect to the N.O. terminal if you want the path to be OPEN during a power failure.

Your choice for wiring the output contacts also determines how to set the fail-safe DIP switches for

proper operation (see 5.2.3 - Setting the Digital Output DIP Switches).

Figure 11 Form C output contact wiring

To connect an output:
1. Disconnect electrical power from the Expansion Board.
2. If necessary, remove a conduit knockout to permit wire entry into the Expansion Board enclosure.
3. Bring the wire(s) into the Expansion Board enclosure through a conduit knockout or access slot.
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.
5. Tighten the screw until it holds the wire snugly.

!

WARNING

“RISK OF ELECTRIC SHOCK” - Hazardous voltage may be present. More than one

disconnect switch may be required to de-energize the equipment before servicing.

!

CAUTION

The Expansion Board is designed for use on properly grounded (earthed) 24VAC Class 2

power, 50Hz or 60Hz. The ground wire for the power lead must be wired to the earth ground

terminal (stud located next to the 24VAC terminal block). This equipment is intended to be

installed by a qualified and certified electrician who must review and approve customer-

supplied wiring and circuit breakers, verify correct input and grounded (earthed) connections

to ensure compliance with technical standards and national and local electrical codes.
Segregate and install separate electrical conduits for non-class 2 circuits in accordance with

local building codes.

V2

V4

V6

V8

V10

V12

V14

V16

Multiflex

1

810-306

5

USE COPPER (CU) CONDUCTORS ONLY.

D6

POWER INPUT

RELAY OUTPUTS

Numbering

keys

OUTPUT TERMINAL BLOCKS - Note numbering keys above terminal blocks;

outputs are numbered from left (9) to right (16)

N.C.

N.O.

Wire connected

to N.C. terminal:

Relay is CLOSED

on power failure

N.C.

N.O.

Wire connected

to N.O. terminal:

Relay is OPEN

on power failure

One wire MUST

be connected to

middle terminal