1 wiring specifications, Iring, Onnections – Liebert Universal Monitor User Manual

Page 33: Ptional, Xpansion, Oard, Wiring specifications, Table 9, Wiring specifications - optional expansion board, Wiring and connections

Advertising
background image

Wiring and Connections - Optional Expansion Board

25

5.0

W

IRING

AND

C

ONNECTIONS

- O

PTIONAL

E

XPANSION

B

OARD

5.1

Wiring Specifications

Input and output connections to the optional Expansion Board may be made in any order—it is not

necessary, for example, to make all input connections before making any output connections. Use cop-

per conductors only for all wiring.

!

CAUTION

Remove all power before installing any wiring to the Expansion Board or changing input or

output connections.

!

WARNING

“RISK OF ELECTRIC SHOCK” - More than one disconnect switch may be required to

de-energize the equipment before servicing.

Table 9

Wiring specifications - optional Expansion Board

Connection

Supported Wire Type

Maximum Wire Length

Rating

Digital

Input

18-22 AWG Stranded & Unshielded

18 AWG* (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

750 ft. (225m)

Dry Contact

(24VDC,

10 mA)

Digital

Output

18-22 AWG Stranded & Unshielded

18 AWG* (recommended)

Non Plenum - Belden 9740

Plenum - Belden 89740

18 AWG*

(recommended)

20 AWG

22 AWG

240VAC,

2A max.

@3A 50 ft. (15m)

@2A 100 ft. (30m)

@1A 200 ft. (60m)

@3A 40 ft. (12m)

@2A 60 ft. (18m)

@1A 100 ft. (30m)

@3A 25 ft. (7m)

@2A 35 ft. (10m)

@1A 75 ft. (23m)

Communication

EIA485

18-22 AWG Stranded & Shielded

22 AWG* (recommended)

Non Plenum - Belden 9461

Plenum - Belden 88761

3000 ft. (900m)

N/A

24VAC Power

Connection

(TB1)

18-22 AWG Stranded & Shielded

18 AWG* (recommended)

Non Plenum - Belden 8770

Plenum - Belden 88770

150 ft. (45m)

24VAC

@0.6A

* Recommended

Advertising