7 setup system - setup output, Table 25 default settings - digital outputs, 1 change label (name of output) – Liebert Universal Monitor User Manual

Page 66: Setup system - setup output, Change label (name of output), Define main board output as normally open / closed, Table 25, Default settings - digital outputs, Setup output

Advertising
background image

System and Control Options

58

9.7

Setup System - Setup Output

The Universal Monitor has eight outputs that may be configured indi-

vidually. If the optional Expansion Board is used, its additional eight

digital outputs may be renamed. The outputs may have a wide variety

of Liebert or other manufacturers’ equipment connected for configured

responses to input alarms and events.
To configure an output:
Log In and Choose Setup System

• From the Main Menu, use the arrows

↑ ↓

to

choose System and

Control, then press Enter ↵ (see 9.1 - Login for help).

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑ ↓

to

choose

Setup System, then press Enter ↵ .

Select an Output to Configure

• From the Setup System Menu, shown at right, use the arrows

↑ ↓

to

choose Setup Output and press Enter ↵ .

• From the Select Output Menu, choose the output you want—for

example, Output01—and press Enter ↵ .

Table 25 shows digital output features and default settings. You may

change the name of any output. In addition, the Universal Monitor’s

eight outputs may be defined as normally open or closed.
Use the steps following Table 25 to change the default settings for any

digital output.

9.7.1 Change Label (Name of Output)

Each output has a default label (Output01, Output02, etc.) that you

may change to a more descriptive name. The label may consist of up to

eight characters (see Table 20 for valid characters).

• From the Setup Output Menu, as shown at right, use the

arrows

↑ ↓

to

choose Change Label for the selected output and

press Enter ↵ .

• To change the output’s label, which may consist of up to eight char-

acters:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.

• When finished, press Enter ↵ again.

9.7.2 Define Main Board Output as Normally Open / Closed

Each output may be set up as Normally Open (NO) or Normally Closed

(NC). The default setting for all output points is NO (Normally Open).

• From the Setup Output Menu, choose Change State, as shown at

right, and press Enter ↵ .

• To change the normal state for this output, use the arrows

↑ ↓

to

choose NO (Normally Open) or NC (Normally Closed), then press

Enter ↵ .

Table 25

Default settings - digital outputs

Feature

Default

Other Options

LABEL

OUTPUT01

Any name (up to eight

characters)

NORM OPEN/CLOSE

(Main board only)

NO (Normally open)

NC (Normally closed)

Setup System Menu

SETUP INPUT
SETUP COMMON ALARM
SETUP SENSOR
SETUP I/O MATRIX

↑ ↓=NEXT

=SELECT

> SETUP OUTPUT

SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP EXP BOARD

Select Output Menu

SELECT OUTPUT

> OUTPUT01

NO

OUTPUT02

NO

↑ ↓=NEXT

=SELECT

OUTPUT03

NO

OUTPUT04

NO

OUTPUT05

NO

OUTPUT06

NO

OUTPUT07

NO

OUTPUT08

NO

OUTPUT09

NO

OUTPUT10

NO

OUTPUT11

NO

OUTPUT12

NO

OUTPUT13

NO

OUTPUT14

NO

OUTPUT15

NO

OUTPUT16

NO

NOTE: OUTPUT09-OUTPUT16

for optional Expansion Board

Setup Output Menu

> CHANGE LABEL

CHANGE STATE

↑ ↓=NEXT

=SELECT

Change Label

CHANGE LABEL

LABEL: OUTPUT01

↑ ↓=SELECT

=NEXT/END

Setup Output Menu

CHANGE LABEL

> CHANGE STATE

↑ ↓=NEXT

=SELECT

Change State

SET TO NORMAL OPEN
OR NORMAL CLOSE? NO

↑ ↓=NO/NC

=END