Installation - Main Board

14

2.4.2 Termination and Mounting - Large Enclosure

Input Power Connections

To connect electrical power to the Transformer Module:
1. Install electrical wiring from utility power to the Transformer Module.
2. Use copper wires only; proper wiring to use for power is 14/2 AWG copper wire with ground.
3. For the TM230 only: strip wires 3/8" (9.6mm).

Note: For the TM115, wires are pre-stripped 0.4" (10.2mm) at the factory.

4. Connect the wiring as follows:

5. Secure the incoming electrical service wires to the TM115 input wires with wire nuts as shown in

Figure 7 or to the TM230 connectors as shown in Figure 8.

24 VAC Output Power Connections

To connect to the 24VAC outputs:
1. Install electrical wiring from device requiring 24VAC power to the Transformer Module.
2. Use copper wire only; proper wiring to use for power is 18, 20 or 22 AWG copper wire. Strip

wire 1/4".

3. There are two 24 VAC output connectors (TB1 and TB2). Terminate wires to the connector as

shown in Figures 7 and 8. TB1 and TB2 are NOT polarity sensitive.

4. Secure the wires to the connector.

!

CAUTION

The 115VAC/230VAC Transformer Module must be connected to a branch circuit with 15A

branch circuit protection.
This equipment is intended to be installed by a qualified and certified electrician who must

review and approve customer supplied wiring and circuit breakers, verify correct input and

grounded connections to ensure compliance with the technical standards and national and

local electrical codes.
The Transformer Module shall be used only as indicated by the manufacturer.

!

WARNING

Be sure that the Power On/Off switch is set to OFF before installing any wiring to this unit.

The switch is at the bottom of the unit.

TM115

TM230

Connection Type

White wire

Neutral (L2)

Neutral

Black wire

Line (L1)

Power (Line)

Green wire

Ground lead

Ground

Figure 7

Power wiring to TM115

Figure 8

Power wiring to TM230

Knockout for

external wiring

Wire nuts

connecting

electrical

wiring

TM115

24VAC output

(TB1)

Ground

TM230

Line (L1)

Neutral (L2)

Knockout for

external wiring

24VAC output

(TB1)

Ground