System and Control Options

77

2. The firmware update is a two-step process—this step describes how to upload the file

prog###.s19 (where ### is a number—for example, prog118.s19) to the Universal Monitor:
a. At the top of the HyperTerminal window, shown below, click on Transfer, then on Send File.

b. In the Send File window, as shown above:

• In the Filename box, enter the full path of the file to be uploaded—prog###.s19—or click

on the Browse button to locate the file.

• In the Protocol box, select Xmodem from the drop-down list.
• Click on the Send button. (To close the window without sending the file, click on Close or

Cancel.)

• When the transfer is complete, a confirmation message appears in the Service Terminal

Interface window.

3. Next, follow these steps to upload the file flash###.s19 (where ### is a number—for example,

flash607.s19) to the Universal Monitor:
a. At the top of the HyperTerminal window, shown above, click on Transfer, then on Send File.
b. In the Send File window, shown above:

• In the Filename box, enter the full path of the file to be uploaded—flash###.s19—or click

on the Browse button to locate the file.

• In the Protocol box, select Xmodem from the drop-down list.
• Click on the Send button. (To close the window without sending the file, click on Close or

Cancel.)

• When the transfer is complete, a confirmation message—“Firmware Update Successful”—

appears in the Service Terminal Interface window and the Universal Monitor reboots

with the new firmware update.

NOTE
The following instructions refer to the Microsoft Windows HyperTerminal program. These

steps may vary for other communications programs.

Select

Xmodem

Enter filename -

prog###.s19 or

flash###.s19

Send button

Advertising