System and Control Options

50

9.5.1 Identify the Sensor as Connected

To make use of an analog sensor, you must specify it as Connected (Y).

By default, analog sensors are Not connected (N).

• From the Setup Sensor Menu, choose Connected, as shown at

right, and press Enter ↵ .

• To change this feature, use the arrows

↑ ↓

to

choose Y (Yes - Con-

nected) or N (No - Not connected), then press Enter ↵ .

9.5.2 Change Sensor Label (Name)

Each sensor has a default label (Sensor_1, Sensor_2, etc.) that you may

change to a more descriptive name. The label may consist of up to eight

characters (see Table 20 for valid characters).

• From the Setup Sensor Menu, choose Label for the selected sen-

sor—Label: Sensor_1 in the example—and press Enter ↵ .

• To change the sensor’s label, which may consist of up to eight char-

acters:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.

9.5.3 Change Units Label

For each sensor, you may use a three-character label to specify mea-

surement units, such as DEG (see Table 20 for valid characters).

• From the Setup Sensor Menu, choose Units for the selected sensor

and press Enter ↵ .

• To enter the units label, which may consist of up to three charac-

ters:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.

Setup Sensor Menu

SETUP SENSOR_1

> CONNECTED : N

LABEL: SENSOR_1

↑ ↓=NEXT

=SELECT

UNITS: ___
4 mA: -999.9
20 mA: +999.9
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: -0999.9
HIGH SETPT: +0999.9
SENSOR DELAY: 00:01

Sensor Connected

IS THE SENSOR
CONNECTED? N

↑ ↓=Y/N

=END

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED : Y

> LABEL: SENSOR_1

↑ ↓=NEXT

=SELECT

UNITS: ___
4 mA: -999.9
20 mA: +999.9
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: -0999.9
HIGH SETPT: +0999.9
SENSOR DELAY: 00:01

Change Sensor Label

CHANGE SENSOR LABEL

LABEL: ROOM TMP

↑ ↓=SELECT

=END

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED : Y
LABEL: ROOM_TMP

↑ ↓=NEXT

=SELECT

> UNITS: ___

4 mA: -999.9
20 mA: +999.9
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: -0999.9
HIGH SETPT: +0999.9
SENSOR DELAY: 00:01

Change Units Label

CHANGE UNITS LABEL

UNITS: DEG

↑ ↓=SELECT

=NEXT/END