9.3.1 Change Label (Name of Input)

Each input has a default label (Input_01, Input_02, etc.) that you may

change to a more descriptive name for ease in recognizing alarms and

events associated with the input. The label may consist of up to eight

characters (see Table 20 for valid characters).

• From the Setup Input Menu, choose Label for the selected

input—Label: Input_01 in the example at right—and press

Enter ↵ .

• To change the input’s label, which may consist of up to eight char-

acters:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.

9.3.2 Define Input as Normally Open or Normally Closed

Each input may be set up as Normally Open (NO) or Normally Closed

(NC). The default setting for all input points is NO (Normally Open).
If you require an input to be a supervised point, define the input as

Normally Closed (NC).

• From the Setup Input Menu, choose Norm Open/Close, as shown

at right, and press Enter ↵ .

• To change the normal state for this input, use the arrows

↑ ↓

to

choose NO (Normally Open) or NC (Normally Closed), then press

Enter ↵ .

9.3.3 Define Input as Alarmable or Event

Each digital input may be defined as Alarmable (AL) or as an

Event (EV).

• For a digital input defined as alarmable, the following alarm reac-

tions occur when the status of the monitored input device changes:

the LCD flashes, the audible horn sounds, configured pager num-

bers will be notified and a record is entered in the Alarm Log.

• For a digital input defined as an event, the status change is

recorded in the Event Log.

By default, all digital inputs are set up as AL (Alarmable).

• From the Setup Input Menu, choose Alarm/Event, as shown at

right, and press Enter ↵ .

• To change the type of digital input, use the arrows

↑ ↓

to

choose

AL (Alarmable) or EV (Event), then press Enter ↵ .

Setup Input Menu

SETUP INPUT_01

> LABEL: INPUT_01

NORM OPEN/CLOSE: NO
ALARM/EVENT: AL

↑ ↓=NEXT

=SELECT

LATCHED: N
DELAY: 00:01

Change Label

CHANGE LABEL

INPUT_01

↑ ↓=SELECT

=NEXT/END

Setup Input Menu

SETUP INPUT_01

LABEL: INPUT_01

> NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

↑ ↓=NEXT

=SELECT

LATCHED: N
DELAY: 00:01

Normally Open / Closed

IS INPUT NORMALLY
OPENED OR CLOSED? NO

↑ ↓=NO/NC

=END

Setup Input Menu

SETUP INPUT_01

LABEL: INPUT_01
NORM OPEN/CLOSE: NO

> ALARM/EVENT: AL

↑ ↓=NEXT

=SELECT

LATCHED: N
DELAY: 00:01

Alarmable / Event

IS INPUT AN ALARM
OR EVENT? AL

↑ ↓=AL/EV

=END