0 specifications, 1 universal monitor specifications, Pecifications – Liebert Universal Monitor User Manual

Page 91: Universal monitor specifications

Advertising
background image

Specifications

83

10.0 S

PECIFICATIONS

10.1 Universal Monitor Specifications

Power

Requirements

Small Enclosure

Large Enclosure

NOTE

UMS02400

115VAC

UML11500

230VAC

UML23000

If the equipment is

used in a manner

not specified by the

manufacturer, the

protection provided

by the equipment

may be impaired.

24VAC ±10%

of nominal;

50/60 Hz, 1.3A,

30VA

115VAC ±10%

of nominal;

60Hz, 4A,

460VA

230VAC ±10%

of nominal;

50Hz, 0.5A,

115VA

Dimensions

W x D x H, in. (mm)

14-1/4 x 2-3/4 x 12

(361.95 x 69.85 x 304.8)

18 x 2-3/4 x 18

(457.2 x 69.85 x 457.2)

Weight (Assembled)

7.68 lb. (3.48 kg)

20.56 lb. (9.33 kg)

Enclosure Type

NEMA 1

Liquid Crystal Display (LCD)

Four line, 20 character, backlit

Mounting Surface

Building Wall or Structural Member

Ambient Operating

Environment

32ºF to 104ºF (0ºC to 40ºC)

0% RH to 95% RH (non-condensing)

Processor Specifics

Model

Motorola XC68HC812A4

Clock speed

16MHz

Total RAM

256Kb

Total FLASH

4M

Total EEPROM

4K

A/D Resolution (Analog IN)

12 Bit

Modem Type

Embedded 14.4K bps

Clock Type

Real-Time Clock

Clock battery backup type

Lithium Cell (non-replaceable)

Clock battery life

7 years, constant, no power

Modem battery backup type

Nickel Cadmium (replaceable)

Modem battery life

10 minutes at full load

Communications

Local Communications

RS232

Remote Communications

Modem (9600-N-8-1)

Supported pagers

Baud rate 9600 bps, Parity=None, Data bits=8, Stop bits=1

9600 E-7-1 supports TAPI protocol version 1.8

SiteScan Web

IGM Protocol, EIA422

Expansion Board (optional)

EIA485

Agency Listings

No Transformer Module

With Transformer Module

(UMS02400)

115VAC

(TM115)

230VAC

(TM230)

UL

UL3121

UL1012

UL1585

CSA

C22.2 No. 1010

C22.2 No. 66 and

C22.2 No. 107.1

CE

Yes

Yes

FCC Compliance

CFR 47 Part 15

N/A

Inputs & Outputs (Quantity)

Digital Inputs (8)

Dry Contact Closure 24VDC, 10 mA

Analog Inputs (4)

4-20 mA signal input with selectable

power source of 12VDC or 24VDC

Digital Outputs (8)

24VAC, 3A

Common Alarm Outputs (2)

24VAC, 3A

Advertising