TROUBLESHOOTING & REPAIR
F-40
F-40
COMMANDER 300
STATOR VOLTAGE TEST
(continued)
FIGURE F.16 – AUXILIARY LEAD TEST LOCATION
AUXILIARY
LEADS #3, #5, #6
(BEHIND PANEL)
AUXILIARY POWER AND WELD
WINDINGS TEST
1.
Start the engine and run at high idle (1900
RPM). Do not load welding or auxiliary
power.
2.
Check for 115-132VAC at leads #3 to #5.
Also check for 115-132VAC from leads #6 to
#5. See the Wiring Diagram.
3.
Check for 230 to 264VAC at leads #3 to #6.
See the Wiring Diagram.