Sps current consumption, Sps current consumption -3, Sps specifications – Tyco 4100U User Manual

Page 103

Advertising
background image

6-3


• +24V Sig is used to supply the NACs. It can be made accessible by

configuring a NAC as an aux power output (normally energized). The PDI
has a 24V Sig bus that is only powered when an SPS is plugged directly on
to it. (Not in standard configuration). The 4100 MXP is the only Australian
approved card that takes power from this bus. All other cards draw power
from +24V Card.

• The battery circuit is supervised every 29 seconds. The battery test (custom

control) is for 1 hour once per week.

• The battery is connected to the charger but is normally disconnected from the

bulk supply. During mains fail, and the 1 hour battery test, the battery gets
connected to the bulk supply.

• The IDNet output is 30V in the normal condition as is used to prolong battery

standby. When it is necessary to activate large numbers of output devices on
IDNet peripherals (such as piezo sounders), the output voltage is increased
to 35V to provide sufficient voltage at the end of line to activate the piezo.
The higher voltage state is an alarm condition for the purpose of standby
battery calculation.

The following table summarizes battery standby capabilities for the SPS. Voltage
assumed is 24 V, which is the rated battery voltage for lead-acid type batteries.

Table 6-2. SPS Current Specifications

Standby Conditions

Current

• No alarms (NACs normal)

• IDNet LED ON, no IDNet devices connected

175 mA

Add to above for each additional set of 50 IDNet devices in
standby, with IDNet at 30 V

40 mA

Total current for fully loaded IDNet channel (250 devices) in
standby

375 mA

Alarm Conditions

Current

• 3 NACs ON

• IDNet LED ON, no IDNet devices connected

185 mA

Add to above for each set of 50 IDNet devices in alarm, 20
LEDs ON

80 mA

Add to above for each set of 50 IDNet devices in alarm, LEDs
OFF

50 mA

Total current for a fully loaded IDNet channel (250 devices) in
alarm, 20 LEDs ON

475 mA

Notes:
Additional standby conditions: Trouble relay activated, power trouble LED

on, IDNet LED on, battery charger off, auxiliary power load = 0 mA

Additional alarm conditions: Trouble relay activated, power trouble LED

on, IDNet LED on, battery charger off, auxiliary power load = 0 mA, NAC
alarm load = 0 mA, IDNet = 35 V

Continued on next page

SPS Specifications,

Continued

SPS Current
Consumption