Class b nac wiring, Power supply wiring distances, Overview – Tyco 4100U User Manual

Page 113: Class b nac wiring -5, Power supply wiring distances -5, Overview -5, Figure 7-3, Class b wiring -5, And 4 mm

Advertising
background image

7-5

To connect the SPS to appliances using Class B wiring, read the following instructions
and refer to the figure below.

1. Route wire (between 0.75 mm

2

and 4 mm

2

) from the B+, B- outputs on TB2 of

the SPS to the appropriate inputs on a peripheral notification appliance. Use
NAC1, NAC2, or NAC3, as configured.

2. Route wire from the first appliance to the next one. “T” tapping is not allowed.

Repeat for each appliance.

3. Route wire from the last appliance to the supplied EOLR or a 4081-9008 EOL

Harness (10 K Ohm, ½ W; brown/black/orange).

4. Repeat steps 1 through 3 for each NAC output you want to use.

5. Leave the 378-030 EOL Resistor (10 K Ohm, ½ W; brown/black/orange) on

each unused circuit. The circuit must connect “B+” to “B-” terminals.

6. If the appliance/device to be used does not have an integral diode, a blocking

diode must be fitted between the incoming +ve wire and the +ve terminals of the
device with cathode to the device.


The illustration below shows Class B wiring.

P1

3
2

1

B+ B- A+ A-

TYPICAL

APPLIANCE

RED

BLK

NAC1

B+ B- A+ A-

NAC1

B+ B- A+ A-

NAC1

LED1

LED2

LED3

TYPICAL

APPLIANCE

10K 1/2W (133-894)

NAC2

NAC3

RED

RED

RED

RED

Figure 7-3. Class B Wiring



Before wiring from any type of power supply to notification appliances, check Tables 7-1
and 7-2 for wiring distances.

Class B NAC Wiring

Power Supply Wiring Distances

Overview

Important: Conductors must test free of

all grounds.

0.75 mm

2

to 4 mm

2

BLK

BLK

BLK

4081-9008 EOL Harness

Leave the 378-030 EOL
Resistor (10 K Ohm, ½ W;
brown/black/orange) on
unused B+/B- terminals

Ferrite bead

required for CE

compliance. Use

SX0005 or kit

4100-5129.

Advertising