Miniplex system guidelines (non-4100u), Overview, Guidelines – Tyco 4100U User Manual

Page 62: Miniplex system guidelines (non-4100u) -34, Overview -34, Guidelines -34

Advertising
background image

3-34


The rules on this page apply exclusively to MINIPLEX systems. Review each guideline
before installing a MINIPLEX 4100 system.

• The Style 4 RUI card supports MINIPLEX transponders and 4602/4603 serial

annunciators on the same signaling line circuit.

• Up to 4 RUI cards in the 4100 Control Panel can be used for distributing transponder

wiring in different directions or for supporting different wiring requirements (such as
using a Style 7 RUI for serial annunciators).

• Up to 31 MINIPLEX transponders can be controlled from the 4100 Control Panel,

and can be distributed as required among the RUI cards.

• “T” tapping is not allowed unless less than 40 detectors/addressable devices are

connected to the MINIPLEX.

• Wiring from RUI cards is a minimum of 18 AWG (0.75sqmm) twisted, shielded pair.
• The maximum wiring distance from the 4100 RUI card to a MINIPLEX transponder

is 2500 feet (762 m). For Style 4 wiring, this can be extended to 10,000 feet (3 km)
maximum if “T” tapping is used.

MINIPLEX System Guidelines (Non-4100U)