To connect addressable devices/detectors to the SPS IDNet using Class B wiring, read the
following instructions.

1. Under AS1670.1 Class B wiring is allowed only for a maximum of 40

addressable devices.

2. A ferrite bead is required on the SPS IDNet cable.
3. On TB1, jumper B+ to A+, and jumper B- to A-.

4. Route wire (between 0.75 mm

2

and 4 mm

2

) from the B+, B-.

The illustration below shows Class B wiring.

B+ B- SHLD

IDNet

A+

P1

3
2

1

A-

IDNet LINES TO DEVICES

(CLASS B / STYLE 4)

Figure 7-7. Class B Wiring


SPS IDNet Wiring,

Continued

Class B Wiring

Ferrite bead

required.