Configuration, Notes, Warning – Tyco 4100U User Manual

Page 108: Specification, Configuration -8, Notes -8, Warning -8, Specification -8, The alarm relay card

Advertising
background image

6-8


The relays have one set of voltage-free contacts (see note below) connected to one pair of
terminals via a header. The two terminals are configured for normally closed or normally
open by positioning a jumper on the header.

Table 6-3. Alarm Relay Card Jumper Positions

Relay Header

Normally

Closed Normally

Open

Alarm
Isolate (Supervisory)
Fault (Trouble)

P1
P2
P3

1-2 (top)
1-2 (top)
1-2 (top)

2-3 (bottom)
2-3 (bottom)
2-3 (bottom)


• The common contact of each relay has a transient suppressor to earth, and must not be

used to switch voltages greater than its rating.

• The common contact is protected with a 3A fuse.

• For default configuration the relays are normally de-energised and energise on

Fault/Isolate/Alarm.

• The corresponding LED illuminates when the relay is energized.

• The relays may be configured under custom control to operate other than default.

If relay RL3 is configured for operation other than Fault (Trouble), jumper P3 on the SPS
must be shifted to positions 1-2 (top).

CARD

Input Voltage

20-32Vdc

Input Current

15mA @ 24V, quiescent

(nominal)

37mA @ 24V, all relays on

RELAYS

Form

Voltage-free changeover, suppresses to
earth

Voltage 30Vac,

32Vdc

Current

2A, resistive load

FUSE

F1, F2, F3

5 x 15mm, Glass Cartridge, 3A (208-163)



The Alarm Relay Card,

Continued

Configuration

Notes

Warning

Specification