The following lists the addressable devices approved for use with IDNet and
shows current rating and numbers allowed per loop.

Device Type

Operating

Current mA

Maximum

Addressable

Point On

Analogue Loop

Maximum

Addressable

Points on

Analogue Line

4090-9116

IDNet Comms Isolator

0.5

(2 with LED on)

250 40*

4090-9118

Relay IAM with T-sense

0.5

(2 with LED on)

250 40*

4090-9117

Addressable Power

Isolator

0.5

(2 with LED on)

250 40*

4090-9118

Relay IAM with T-Sense

Input

0.5

(2 with LED on)

250 40*

4090-9119

Relay IAM with

unsupervised Input

0.5

(2 with LED on)

250 40*

409-9120

6 Point I/O

0.5 250 40*

4090-9001

Supervised IAM

0.65

(2.8 with LED

on)

250 40*

4090-9101

Monitor ZAM

0.65

(2.8 with LED

on)

250 40*

4099-9032

Manual Call Point

0.65

(2.8 with LED

on)

250 40*


* Maximum allowed by AS1670.1.

The maximum specified loop/line resistance is 40

Ω.


The maximum number of LEDs switched on by an IDNet in alarm is 20.

The 6 Point I/O LED is powered from the external 24V supply, not from the loop.

Note: The relays on the 6 Point I/O are not approved for switching field loads,
i.e. the

contacts may only be used to switch loads within an earthed

cabinet.