H-1


System Capacity

2,000 points of addressable points, plus 2,000 points of

annunciation. Expansion

Up to capacity above.

Up

to

119

Addressable

cards

Cabinet

Size

Dependent

on

system

configuration

Cabinet Material

1.6mm Zintex

Cabinet Finish

Powder coated

Cabinet Colour

Cream Wrinkle

Mounting Wall

mount


Mains Input

240V AC, +6%, -10%, 50Hz

Internal Power Supply

24V DC @ 9A

Standby Battery

24V sealed lead acid up 110Ah

Battery Charger

27.3V DC (nominal)

PSU Supervision

Charger high/low, Battery low/fail

Temperature

-5

°C to 45°C

Humidity

10% to 90% RH non-condensing


Refer to Table 6-1, 6-2 for full SPS specifications.


Alarm Relay Card
F1 Alarm, 3A, 15 x 5mm, Glass Cartridge
F2 Supervisory, 3A, 15 x 5mm, Glass Cartridge
F3 Trouble, 3A, 15 x 5mm, Glass Cartridge

Fused Distribution Board (if fitted)
F1 24V Out, 1A 20 x 5mm Glass Cartridge
F2 24V Out, 1A 20 x 5mm Glass Cartridge
F3 24V Out, 1A 20 x 5mm Glass Cartridge
F4 24V Out, 1A 20 x 5mm Glass Cartridge

WALK TEST System Test

4 Operator Access Levels

Event Historical Logging

Device selectable Alarm Verification

Individual Zone Isolate

Addressable device disable/enable

Non-volatile Flash EPROM for field editable program changes

Expansion cards firmware upgraded via download to flash EPROMs