Configuring the card consists of selecting the shield tie point, and setting the device
address..

If a shielded cable is used, connect the cable shield to the dedicated terminal on TB1 and
use jumper port (P1) to select where the shield will be tied.

• Position 1 - 2 connects the shield to 0 V.
• Position 2 - 3 connects the shield to Earth.

The device address is set on DIP switch SW1, which is a bank of eight switches (see
figure below). From left to right, these switches are designated as SW1-1 through SW1-8.
The function of these switches is as follows:

SW1-1. This switch sets the baud rate for the internal 4100 communications

line running between the card and the 4100 CPU. Set this switch to ON.

SW1-2 through SW1-8. These switches set the card’s address within the

4100 FACP. Refer to the table in Appendix A for a complete list of the switch
settings for all of the possible card addresses.


Note: You must set these switches to the value assigned to the card by the

4100 Programmer.






1

8

7

6

5

4

3

2

Figure 8-4. DIP Switch SW1



Configuring the Card

Overview

Setting the Shield
Tie Point

Setting the Address

ON

OFF

Dip Switches SW1-2 through
SW1-8 set the Card Address.
Figure shows an Address of 3.

4100 Comm. Baud Rate.
Switch (SW1-1)
Must Be Set to ON