Connecting loops, System design, Network communication – Tyco 4100U User Manual

Page 25: Connecting loops -7, System design -7, Network communication -7, Figure 1-4, Interconnected loop configuration, Network configuration, Continued

Advertising
background image

1-7


Network loops can be joined via physical bridge cards. There may be no more than two
Style 7 network loops (two hub configurations) connected in tandem. For every two
loops that are interconnected (using one physical bridge), there can be a maximum of
three physical bridges used in a star configuration. See Figure 1-4.

Remote Loop

Physical Bridge Link

Local Loop

Physical Bridging

(Star Configuration)

Graphic Command

Center (GCC)

Physical

Bridge

Link

Physical Bridge Link

Hub Node

Hub

Node

Remote

Node

Physical Bridge Link

Figure 1-4. Interconnected Loop Configuration

To be used as a network node, a 4100 panel must contain the following:

• CPU
• System Power Supply
• 4100 Network Interface Card
• Optional slave cards

Network communication is achieved via 4100-6014 or 4100-6035 Network Interface
Cards (NICs). Each network node requires a NIC. Once the FACP is a network node, it
may be programmed to be fully in control of other nodes, or to be fully passive, or
anywhere in between.

Network Configuration,

Continued

Connecting Loops

System Design

Network
Communication