Rui communication, Rui communication -5, Figure 1-2 – Tyco 4100U User Manual

Page 23: Miniplex 4100u system, Miniplex configuration, Continued

Advertising
background image

1-5


The 4100 internal comms bus may be used to carry data from the CPU in the main cabinet
to expansion equipment in a co-located cabinet. 4100 data from the CPU may be routed to
remote cabinets (RTUs) in a MINIPLEX system by using the external RUI comms bus.
An RUI line, routed from either the CPU Motherboard in the 4100U, or the RUI card in
the 4100, allows the data to travel long distances. Once the RUI line terminates at a
remote cabinet, the TIC (4100U) or RIC (4100) in that cabinet distributes the CPU’s data
to the other modules within the cabinet.

Power has to be supplied locally within each RTU, or routed from the main FIP.
Figure 1-2, below, outlines this process in a typical MINIPLEX setup.

4100U

RUI Risers - 4 MAX (same channel)

(from CPU Motherboard or Remote

Unit Interface Card)

Transponders may be located

further apart (within the 2500'

limit) as called for by the

application requirements.

Risers from 4100U to

Remote Transponders

RUI

9th Floor
Transponder
Unit

6th Floor
Transponder
Unit

3rd Floor
Transponder
Unit

RUI I/F

Slave

Slave

Slave

RUI I/F

Slave

Slave

Slave

RUI I/F

Slave

Slave

Slave

Note:
Although not shown, nested
RUI is supported up to one
level deep.

Figure 1-2. MINIPLEX 4100U System

MINIPLEX Configuration,

Continued

RUI Communication

Advertising