Class a nac wiring table, Class a nac wiring table -6 – Tyco 4100U User Manual

Page 114

Advertising
background image

7-6

Table 7-1 lists the maximum distances from the NAC terminal block to the last appliance
in a Class A configuration, depending on wire gauge and current. Use Table 7-1 to
calculate wire distances for your application if you are using Class A wiring.

Table 7-1. Class A Wiring Distances

Alarm

Current @

24 V

Max Distance

w/ 18 AWG

(0.8231 mm

2

)

Max Distance

w/ 16 AWG

(1.309 mm

2

)

Max Distance

w/ 14 AWG

(2.081 mm

2

)

Max Distance

w/ 12 AWG

(3.309 mm

2

)

DC

Resistance

0.25 A

420 ft. (128 m)

667 ft. (203

m)

1,063 ft. (324

m)

1,691 ft. (515

m)

6 Ohms

0.50 A

210 ft. (64 m)

334 ft. (102

m)

532 ft. (162 m)

845 ft. (258 m)

3 Ohms

0.75 A

140 ft. (43 m)

222 ft. (68 m) 354 ft. (108 m)

564 ft. (172 m)

2 Ohms

1 A

105 ft. (32 m)

167 ft. (51 m)

266 ft. (81 m)

423 ft. (129 m)

1.5 Ohms

1.25 A

84 ft. (26 m)

133 ft. (41 m)

213 ft. (65 m)

338 ft. (103 m)

1.2 Ohms

1.50 A

70 ft. (21 m)

111 ft. (34 m)

177 ft. (54 m)

282 ft. (86 m)

1 Ohm

1.75 A

60 ft. (18 m)

95 ft. (29 m)

152 ft. (46 m)

242 ft. (74 m)

0.86 Ohm

2 A

53 ft. (16 m)

83 ft. (25 m)

133 ft. (41 m)

211 ft. (64 m)

0.75 Ohm

2.25 A

47 ft. (14 m)

74 ft. (23 m)

118 ft. (36 m)

188 ft. (57 m)

0.67 Ohm

2.50 A

42 ft. (13 m)

67 ft. (20 m)

106 ft. (32 m)

169 ft. (51 m)

0.60 Ohm

2.75 A

38 ft. (12 m)

61 ft. (19 m)

97 ft. (30 m)

154 ft. (47 m)

0.55 Ohm

3 A

35 ft. (11 m)

56 ft. (17 m)

89 ft. (27 m)

141 ft. (43 m)

0.50 Ohm


Notes:
• Max Distance = distance from SPS/RPS to last appliance.
• This table is calculated at 49 degrees Centigrade (120 degrees

Fahrenheit). If you are installing in locations that could be exposed to
higher temperatures, refer to NEC Tables 7 and 8 in NFPA code, or
applicable local standard.

• Distances are based on a 3 V drop, and take into account the worst-case

panel output voltage. These distances are worst case to allow for one
single load at the furthest point.

• If circuit integrity wire is used instead of housing cable in a fire-rated

enclosure, reduce wiring distances by 38 feet (12 m) for every 10 feet (3
m) of potential exposure.

• For other wire gauges (e.g. 4 mm

2

) multiply the distance specified for the

nearest wire size by the ratio of the wire area, e.g. for 3A on 4 mm

2

look

up 3A on 12AWG (3.3 mm

2

) and multiply the resulting 43m x 4.0/3.3 =

52m.

Continued on next page

Class A NAC
Wiring Table

Advertising