Class a nac wiring, Class a nac wiring -4, Figure 7-2 – Tyco 4100U User Manual

Page 112: Sps nac field wiring guidelines, Continued

Advertising
background image

7-4


To connect the SPS to reverse-polarity, non-addressable notification appliances using
Class A wiring, read the following instructions and refer to the figure below.

1. Route wire (between 0.75 mm

2

and 4 mm

2

) from the “B+”, “B-”, outputs on TB2

of the SPS to the appropriate inputs on a peripheral notification appliance. Use
NAC1, NAC2, or NAC3 as configured..

2. Route wire from the first appliance to the next one. Repeat for each appliance.

3. Route wire from the last appliance to the A+ and A- inputs on the same NAC

circuit of TB1 of the SPS.

4. Repeat steps 1 through 3 for each NAC output you want to use.

5. Leave the 10 K, ½ W, brown/black/orange resistor (378-030) on each the “B+”

to “B-” terminals of each unused NAC. No external end-of-line resistor is
needed for circuits in use.

6. If the appliance/device to be used does not have an integral diode, a sufficiently

rated blocking diode must be fitted between the incoming +ve wire and the +ve
terminals of the device with cathode to the device.

P1

3
2

1

B+ B- A+ A-

TYPICAL

APPLIANCE

RED

RED

RED

NAC1

B+ B- A+ A-

NAC1

B+ B- A+ A-

NAC1

LED1

LED2

LED3

TYPICAL

APPLIANCE

BLK

BLK

BLK

NAC2

NAC3

Figure 7-2. Class A NAC Wiring

Continued on next page


SPS NAC Field Wiring Guidelines,

Continued

Class A NAC Wiring

SPS NAC Field Wiring Guidelines,

Continued

0.75 mm

2

to 4 mm

2

Important: Conductors must test free of

all grounds.

Leave the 378-030 EOL
Resistor (10 K Ohm, ½ W;
brown/black/orange) on
unused B+/B- terminals

Ferrite beads

required for EMC

compliance. Use

SX0005 or kit

4100-5129.