Wiring illustration, Wiring illustration -40, Figure 3-7 – Tyco 4100U User Manual

Page 68: Miniplex wiring -40, Miniplex wiring (non-4100u), Continued, All wiring is supervised and power limited

Advertising
background image

3-40


The illustration below applies to Class A and Class B wiring.

4100 MINIPLEX MASTER

RIC 11
565-233

MINIPLEX

TRANSPONDER

562-856 W/565-217

COMMS "A"

8

1

COMMS "B"

RUI

T
B
1

T
B
1

RIC 11
565-233

MINIPLEX

TRANSPONDER

8

1

T
B
1

Figure 3-7. MINIPLEX Wiring

Notes:

1. Power wiring is not shown. Connect the RIC II card to the UPS or expansion

power supply in the transponder cabinet.

2. If a UPS is not provided in the transponder cabinet, then 24 V must be

provided from the host panel.

3. Maintain correct polarity on terminal connections. Do not loop wires under

terminals.

4. All wiring is supervised and power limited.







MINIPLEX Wiring (Non-4100U),

Continued

Wiring Illustration

CLASS A

CLASS B

+24 V

24 C

See
Note 1

II II