Fibre Optic Cable Characteristics

All fibre cables shall be multimode, graded index. ST style connectors must be used. No
physical strain shall be put on the cables. There must be no cable bends of less than a
50mm radius.

Two methods are available for joining fibre cable. Splices provide a permanent, very low
loss, fibre-to-fibre connection. Couplers provide temporary connection between two ST
style connectors with a loss of 1.2dB. Both methods are permitted on a fibre Network.

The characteristics of the 4100-0143 fibre optic media card are as follows. Mininium
Launch Power into a 50/125 cable is 50 uW (-13 dBm). Minimum Launch Power into a
62.5/125 cable is 109.5 uW (-8.6 dBm). The maximum value for the minimum input
sensitivity of the receiver is 1.0 uW (-30 dBm).

Maximum line lengths for 50/125 and 62.5/125 cable are shown in the table below.

Fibre CableFibre

CableFib

Loss Per Kilometer

Power Margin

Maximum distance

50/125 Fibre

4 db

4 db

3,050 meters

50/125 Fibre

3 db

3 db

4,500 meters

62.5/125 Fibre

4 db

4 db

4,000 meters

62.5/125 Fibre

3.75 db

3 db

4,500 meters

Table J-2 Network: Maximum Distances, Optical Fibre


All the information above is based on the minimum launch power of the transmitter into
the specified cable and the maximum value of the minimum input sensitivity of the
receiver