Wiring to idnet devices, Overview, Guidelines – Tyco 4100U User Manual

Page 129: Wiring to idnet devices -7, Overview -7, Guidelines -7

Advertising
background image

8-7


Up to 250 IDNet slave devices, such as smoke detectors and manual call points, can be
connected to the IDNet card using Class A (loop) or Class B (line) wiring, with the
following restrictions.

Class A wiring allows the devices to communicate with the IDNet card even in the event
of an open circuit somewhere in the loop. Class A wiring requires that two wires are
routed from the IDNet card to each IDNet device, and then back again to the IDNet card.
Under AS1670.1 every group of 40 devices (or less) must be separated by a Comms
Isolator.

Class B wiring allows “T” tapping, and therefore requires less wiring distance per
installation than Class A. IDNet wiring does not require end-of-line resistors, because
each IDNet device communicates directly to the IDNet card. A maximum of 40 devices
is allowed to be connected this way.

See Appendix F for a list of compatible devices and their ratings.


• Use ferrites. See Fig 7.1.
• Shielded cable is recommended in electrically noisy environments.
• IDNet cabling should not be run adjacent to other cabling, especially non-fire

system cabling, e.g. mains.

• The limiting factors of the 2 core cable connecting the IDNet devices to the

IDNet Card are cable capacitance (attenuates the superimposed coms signal) and
resistance (causes voltage drop of the supply voltage and comms signals).

• The maximum capacitance of 0.58uF core to core must also include the mutual

capacitance of core to earth. The latter is greatly increased when shielded cable
is used.

• Rather than do voltage drop calculations (see notes following), the following

simplified rules are applied.

• Allow a maximum of 40Ω to any device (Class B), and in any loop (Class A)

with 125 devices or less.

• Allow a maximum of 20Ω in any loop with 250 devices.
• Linear de-rating between 40Ω and 20Ω may be applied between 125 devices and

250 devices. Use R

L

= 20

Ω x (1 + (250-n)/125) where R

L

is the allowable line

resistance and n is the number of devices used. E.g. for 200 devices the
maximum resistance allowed may be extended from 20

Ω to: 20Ω + 20Ω x (250

– 200) / 125 = 28

• Use the resistance specifications that apply to the cable being used. The values

used in this manual allow 39

Ω per km for 2 core of 1 mm

2

for copper wire at

49

°C. (A commonly used value is 34Ω per km for 2 core of 1 mm

2

at 20

°C).

See Table 8.1. Note that this includes both cores.

• Sounder bases and 6 point I/O modules do not draw the alarm load from the

loop, but are powered from separate 24V terminals.

• Where devices, e.g. sounder bases, are wired from a 24V source (e.g. supplied

by 24V Aux Power or a NAC), and are in more than 1 zone, the power cable
must also be isolated between zones by a 4090-9117AU Power Isolator Module.

Continued on next page

Wiring to IDNet Devices