Local mode specifications, Local mode specifications -5, Introduction to miniplex transponders (4100u) – Tyco 4100U User Manual

Page 73

Advertising
background image

4-5

Local mode is supported by the following:
• 4100-3101/3104/3105 IDNet Card
• 4100-5101/5102/5103 Expansion Power Supply NACs (including TrueAlert

Non-Addressable SmartSync appliances)

• 4100-5111/5112/5113 System Power Supply NACs (including TrueAlert Non-

Addressable SmartSync appliances)

• 4100-5125/5126/5127 Remote Power Supply NACs (including TrueAlert Non-

Addressable SmartSync appliances)

• 4100-5120/5121/5122 TrueAlert Power Supply NACs
• 4100-1214 to -1225, 4100-1228 to –1239, 4100-1314 to -1325, 4100-1328 to –

1339,
100 W Amplifier NACs

• 4100-1212/1213/1226/1227/1312/1313/1326/1327 Flex 50 Amplifier NACs
• 4009-9401 TrueAlert Addressable Controller
• 4100-1270 Phone Controller and 4100-1272/1273 Phone NAC cards
• 4009-9201/ 9301 IDNet NAC Extender
• 4100-5116 Expansion Signal Card

Local mode is NOT supported by, but can co-exist with, the following:

• 4100 Legacy cards
• 4100-3101 to -3103 Auxiliary Relay Cards
• 4100-6048 VESDA

Interface Kit

• 4100-6043/6044 RS-232/2120 Interfaces
• 4100-1280 to -1287 LED/Switch Annunciators
• 4100-1290 24-Point Graphic I/O Module
• 4602-9101 SCU/ 4602-9102 RCU
• 4603-9101 LCD Annunciator
• 4100-1210/1211/1311 Audio Controller Board
• 4100-6014 Network Interface Card
• 4100-6052 DACT

Bear in mind the following limitations for when local mode is in effect:
• If an alarm is already activated when local mode is initiated, the alarm remains

activated in local mode.

• Software zones are not supported. Basic TrueAlert channels are supported.
• Alarm verification is not supported. All alarms are reported immediately.
• SMPL is not supported.
• TrueAlarm sensors have fixed thresholds.

Continued on next page

Introduction to MINIPLEX Transponders (4100U),

Continued

Local Mode
Specifications