Class b nac wiring table, Class b nac wiring table -7, Power supply wiring distances – Tyco 4100U User Manual

Page 115

Advertising
background image

7-7


Table 7-2 lists the maximum distances from the NAC terminal block to the last appliance
in a Class B configuration, depending on wire gauge and current. Use Table 7-2 to
calculate wire distances for your application if you are using Class B wiring.

Table 7-2. Class B Wiring Distances

Alarm

Current @

24 V

Max Distance

w/ 18 AWG

(0.8231 mm

2

)

Max Distance

w/ 16 AWG

(1.309 mm

2

)

Max Distance

w/ 14 AWG

(2.081 mm

2

)

Max Distance w/

12 AWG

(3.309 mm

2

)

DC

Resistance

0.25 A

840 ft. (256 m)

1,335 ft. (407 m) 2,126 ft. (648 m) 3,382 ft. (1,031 m)

12 Ohms

0.50 A

420 ft. (128 m)

667 ft. (203 m)

1,063 ft. (324 m)

1,691 ft. (515 m)

6 Ohms

0.75 A

280 ft. (85 m)

445 ft. (136 m)

709 ft. (216 m)

1,127 ft. (344 m)

4 Ohms

1 A

210 ft. (64 m)

334 ft. (102 m)

532 ft. (162 m)

845 ft. (258 m)

3 Ohms

1.25 A

168 ft. (51 m)

267 ft. (81 m)

425 ft. (130 m)

676 ft. (206 m)

2.4 Ohms

1.50 A

140 ft. (43 m)

222 ft. (68 m)

354 ft. (108 m)

564 ft. (172 m)

2 Ohms

1.75 A

120 ft. (37 m)

191 ft. (58 m)

304 ft. (93 m)

483 ft. (147 m)

1.71 Ohms

2 A

105 ft. (32 m)

167 ft. (51 m)

266 ft. (81 m)

423 ft. (129 m)

1.5 Ohms

2.25 A

93 ft. (28 m)

148 ft. (45 m)

236 ft. (72 m)

376 ft. (115 m)

1.33 Ohms

2.50 A

84 ft. (26 m)

133 ft. (41 m)

213 ft. (65 m)

338 ft. (103 m)

1.2 Ohms

2.75 A

76 ft. (23 m)

121 ft. (37 m)

193 ft. (59 m)

307 ft. (94 m)

1.09 Ohms

3 A

70 ft. (21 m)

111 ft. (34 m)

177 ft. (54 m)

282 ft. (86 m)

1 Ohm


Notes:
• Max Distance = distance from SPS or RPS to last appliance.
• This table is calculated at 49 degrees Centigrade (120 degrees

Fahrenheit). If you are installing in locations that could be exposed to
higher temperatures, refer to NEC Table 7 and 8 in NFPA code, or
applicable local standard.

• Distances are based on a 3 V drop, and take into account the worst-case

panel output voltage. These distances are worst case to allow for one
single load at the furthest point.

• If circuit integrity wire is used instead of housing cable in a fire rated

enclosure, reduce wiring distances by 38 feet (12 m) for every 10 feet (3
m) of potential exposure.

• For other wire gauges (e.g. 4 mm

2

) multiply the distance specified for the

nearest wire size by the ratio of the wire area, e.g. for 3A on 4 mm

2

look

up 3A on 12AWG (3.3 mm

2

) and multiply the resulting 86m x 4.0/3.3 =

104m.


Continued on next page