Sps auxiliary power wiring, Overview, Guidelines – Tyco 4100U User Manual

Page 116: Sps auxiliary power wiring -8, Overview -8, Guidelines -8

Advertising
background image

7-8


The panel, battery-backed, unregulated dc bulk power is available from the SPS via the
NAC and the 24V Aux power terminals (1 pair only, ref fig 7-4). NACs not configured
as switched outputs may be configured as auxiliary power point type in the 4100
Programmer. All of these are power-limited.

Review the following guidelines before using the SPS for auxiliary power.

• Voltage rating: 24 VDC (nominal), 2 V P-P ripple (maximum).
• The total auxiliary current available for non-alarm is 5 A. The total current available

for the entire SPS is 9 A, including NAC, auxiliary, and card power.

• All wiring is 0.75 mm

2

to 4 mm

2

.

• All SPS powered field wiring requires a ferrite bead (ref fig 7.1).
• All wiring that leaves the building requires overvoltage protection. Install

module
2081-9044 wherever wire enters or exits the building. A maximum of four 2081-
9044 Modules may be connected to one channel.

• When a NAC is configured as an auxiliary power circuit, no end-of-line resistor

is used.

• External wiring is not supervised unless an end-of-line relay is wired, coil to

auxiliary power, and Normally Open contacts are monitored by a system power
point. Relay current must be considered as part of the load.

• Programming is required for the dedicated Auxiliary Power output (TB3).
• The following devices may be connected to the 2 A Auxiliary Power:

-

2088-series relays and door holders

-

2098-series four-wire smoke detectors

-

2190-series monitor and signal ZAMs

- 4090-series

IDNet

ZAMs

-

4098-series four-wire smoke detectors and duct detectors

- 2190-9039

Printer

-

4190-9050/9051 4-20 mA ZAMs

- 4603-9101

LCD

Annunciator

• The Auxiliary Power output is rated at 2 A dc.
• Where multiple loads are to be connected with individual protection, a Fused DC

Distribution board may be fitted directly to the SPS bracket adjacent to TB3.

Continued on next page

SPS Auxiliary Power Wiring