Class a wiring, Class a wiring -13, Figure 7-6 – Tyco 4100U User Manual

Page 121: Sps idnet wiring, Continued

Advertising
background image

7-13


To connect addressable devices/detectors to the SPS IDNet using Class A wiring, read the
following instructions.

1. Ferrite beads are required on the SPS IDNet cables (ref Fig 7.1).
2. Route wire (between 0.75 mm

2

and 4 mm

2

) from the B+, B- outputs on TB1 of

the SPS to the appropriate inputs on a peripheral IDNet device.

3. Route wire from the first IDNet device to the next one. Repeat for each device.

4. Route wire from the last IDNet device to the A+ and A- inputs on TB1 of the

SPS.

B+ B- SHLD

IDNet

A+

P1

3
2

1

A-

IDNet

DEVICE

IDNet

DEVICE

IDNet

DEVICE

IDNet LOOP

(CLASS A / STYLE G)

Figure 7-6. Class A Wiring

Continued on next page

SPS IDNet Wiring,

Continued

Class A Wiring

IDNet

DEVICE

IDNet

DEVICE

IDNet

DEVICE

Ferrite beads

required.