Wiring distances, Related documentation, Wiring distances -12 – Tyco 4100U User Manual

Page 92: Related documentation -12, Figure 5-8, The transient suppressor -12, Step 4. wiring network cards, Continued

Advertising
background image

5-12


• 655-158 Transient Suppressor (ordered as part of 748-599) is required for each

modem-to-telephone line connection.

From Modem

8

5

Grn

Telephone Line

1

4

7

6

2

3

Figure 5-8. The Transient Suppressor

Maximum wiring distances are shown in the Table below and in Appendix J.

Table 5-2. Wiring Distances

Media Type

Size

Data Rate

Max Distance

57.6 kbps

7,000 ft (2,134 m)

24 AWG

(0.2047 mm

2

)

9.6 kbps

12,000 ft (3,658 m)

57.6 kbps

10,000 ft (3,048 m)

Wired

18 AWG

(0.8231 mm

2

)

9.6 kbps

17,000 ft (5,182 m)

50/125 um

57.6 or 9.6 kbps

10,000 ft (3,048 m)

Optical Fiber

62.5/125 um

57.6 or 9.6 kbps

15,000 ft (4,572 m)

57.6 kbps

50 ft (15 m)

RS-232

18 AWG

(0.8231 mm

2

)

9.6 kbps

300 ft (91 m)


Notes:

• The characteristics for 0.75 mm

2

are shown in Appendix J.

• 18 AWG (0.8231 mm

2

) fire-rated twisted, shielded pair must not exceed 58

pF per foot and be less than or equal to 6.385 Ohms per 1,000 feet (305 m).

• 24 AWG (0.2047 mm

2

)

twisted, unshielded telephone cable must not exceed

22 pF per foot and be less than or equal to 25.6 Ohms per 1,000 feet (305
m).

Refer to the 900-242 Field Wiring Specifications or 900-143 Fiber Tutorial for additional
NIC wiring information.

Continued on next page

Step 4. Wiring Network Cards,

Continued

Wiring Distances

Related
Documentation

Transient Suppressor Assembly (655-158)
added to RJ-31x as shown. If connecting to a
terminal block, cut off one end of the cable.
Strip back the cable to connect the two center
wires, normally red and green, to the red and
green wires in the block.