Restricted Breaker Control

13

1.3.1 Setup

Restricted Breaker Control is available but disabled by default. It must be enabled by the factory
or a GE Field Service Engineer. Once enabled, the user controls shown in Figure 1-3 will be
available.

Navigate to the “Restricted Breaker Control” tab from the Main Menu, Maintenance screen -
administrative login is required.

Figure 1-3 Restricted Breaker Control Setting Screen

Open / Close and Trip Code Text Boxes

Enter the code that is required to operate the associated breaker(s) in restricted mode. The
default value for the Open/Close/Trip code is “2.” Allowable values are from 2 to 65535.

Breaker Operation Matrix

Check the operations per breaker which require restricted control.

NOTE: Restricting operations will prevent the HMI from sending said actions to the respective
breaker(s).