Entellisys Status Definitions

2.1 System Status

Modbus TCP clients have access to states of FlexLogic operands, protection elements, breaker
control, status, contact inputs/outputs, and virtual inputs/outputs through the Modbus TCP
interface.

After each protection pass, all the information regarding each operand's state is updated in
corresponding Modbus register. The following sections give a complete list of registers holding
state information of each operand.

NOTE: The 3rd party modbus client must determine which CPU is running as the “active CPU”
(Modbus register: “FlexLogic Active”) and FlexLogic health status (Modbus register: “FlexLogic
Status Message”).

2.1.1 Breaker Status

Each breaker has 13 different states shown in

Table 2-5

. Each one of them corresponds to a

different bit in the data item.

Table 2-5 Breaker Control status bit field

The breaker states for all 30 breakers span across 25 consecutive modbus registers as shown in

Table 2-6

. See

Breaker Control Operand States (25 items) on page 136

for memory locations.

Bit

Value

Notes

0

Breaker Opened

1

Breaker Closed

2

Breaker Locked Out

3

Closing Spring Charged

4

Active Disconnect Connected

5

Active Disconnect Disconnected

6

Secondary Disconnect Connected

7

Breaker Ready

8

Breaker Available

9

Breaker Open Failed

10

Breaker Close Failed

11

Breaker Fault

12

Reserved