Entellisys Status Definitions

30

2

2.1.8 Ground Fault Operand States

Each breaker has 5 different states shown in

Table 2-18

. Each one of them corresponds to a

different bit in the data item.

Table 2-18 Ground Fault status bit field

The breaker states for all 30 breakers span across 12 consecutive modbus registers as shown in

Table 2-19

. See

Ground Fault Operand States (12 items) on page 136

for memory locations.

Table 2-19 Ground Fault status offsets

Bit

Value

0

Trip Pickup

1

Trip Operated

2

Trip Dropout

3

Alarm Pickup

4

Alarm Operated

5

Alarm Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Breaker 1

0

0

Breaker 2

0

6

Breaker 3

0

12

Spans over two registers

Breaker 4

1

2

...

...

...

...

Breaker 30

11

4