2.1.8 Ground Fault Operand States
Each breaker has 5 different states shown in
Table 2-18
. Each one of them corresponds to a
different bit in the data item.
Table 2-18 Ground Fault status bit field
The breaker states for all 30 breakers span across 12 consecutive modbus registers as shown in
Table 2-19
Ground Fault Operand States (12 items) on page 136
for memory locations.
Table 2-19 Ground Fault status offsets
Bit
Value
0
Trip Pickup
1
Trip Operated
2
Trip Dropout
3
Alarm Pickup
4
Alarm Operated
5
Alarm Dropout
Breaker Number
Register
Offset
Bit Offset
Notes
Breaker 1
0
0
Breaker 2
0
6
Breaker 3
0
12
Spans over two registers
Breaker 4
1
2
...
...
...
...
Breaker 30
11
4