CPU External Control Transfer

17

CPU External Control Transfer: High when the active CPU is determined by an external

device through “External Control Transfer.”

Example:

Update VOs to display the Active CPU and indicate the External Control Transfer mode.

1. Reserve 3 spare VOs and add the FlexLogic code shown in figure 1-5.
2. Add indicators to the HMI control screen and map them to their associated VOs.

Figure 1-5 Example: FlexLogic example

Real Time indication

The current active CPU and the External Control Transfer Mode status are displayed at the
bottom of the FlexLogic Editor widow.