Entellisys Status Definitions

26

2

2.1.4 ST Overcurrent Operand States

Each breaker has 3 different states shown in

Table 2-10

. Each one of them corresponds to a

different bit in the data item.

Table 2-10 ST Overcurrent status bit field

The breaker states for all 30 breakers span across 6 consecutive modbus registers as shown in

Table 2-11

. See

ST Overcurrent Operand States (6 items) on page 136

for memory locations.

Table 2-11 ST Overcurrent status offsets

Bit

Value

0

Trip Pickup

1

Trip Operated

2

Trip Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Breaker 1

0

0

Breaker 2

0

3

Breaker 3

0

6

Breaker 4

0

9

Breaker 5

0

12

Breaker 6

0

15

Spans over two registers

Breaker 7

1

2

...

...

...

Breaker 30

5

10