Entellisys Status Definitions

28

2

2.1.6 High Current and High Current Transient Operand States

Each breaker has 3 different states shown in

Table 2-14

. Each one of them corresponds to a

different bit in the data item.

Table 2-14 High Current status bit field

The breaker states for all 30 breakers span across 6 consecutive modbus registers as shown in

Table 2-15

. See

High Current Operand States (6 items) on page 136

and

High Current Transient

Operand States (6 items) on page 136

for memory locations.

Table 2-15 High Current status offsets

Bit

Value

0

Alarm Pickup

1

Alarm Operated

2

Alarm Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Breaker 1

0

0

Breaker 2

0

3

Breaker 3

0

6

Breaker 4

0

9

Breaker 5

0

12

Breaker 6

0

15

Spans over two registers

Breaker 7

1

2

...

...

...

Breaker 30

5

10