Entellisys Status Definitions

36

2

2.1.14 Over (and Under) Demand Metering Alarm Operand States

There are 16 demand alarms. Each alarm relay has 6 different states shown in

Table 2-30

. Each one

of them corresponds to a different bit in the data item.

Table 2-30 Demand Metering status bit field

The Alarm states for all 16 alarms span across 6 consecutive modbus registers as shown in

Table 2-

31

. See

Over Demand Alarm Flex Operand States (3 items) on page 136

and

Under Demand

Alarm Flex Operand States (3 items) on page 136

for memory locations.

Table 2-31 Power Reversal status offsets

Bit

Value

0

Under-Demand Alarm Pickup

1

Under-Demand Alarm Operated

2

Under Demand Alarm Dropout

3

Over-Demand Alarm Pickup

4

Over-Demand Alarm Operated

5

Over-Demand Alarm Dropout

Breaker Number

Register
Offset

Bit Offset

Notes

Alarm 1

0

0

Alarm 2

0

6

Alarm 3

0

12

Spans over two registers

Alarm 4

1

2

...

...

...

Alarm 16

5

10