2headtop - 2.2.3 hrgf detection operand states, 3 hrgf detection operand states – GE Industrial Solutions Entellisys 5.0 Integrator's Guide User Manual
Page 39
Advertising
Multipoint FlexLogic Operand States
39
2
2.2.3 HRGF Detection Operand States
Each breaker has 3 different states shown in
Table 2-36
. Each one of them corresponds to a
different bit in the data item.
Table 2-36 HRGF Detection status bit field
The breaker states for all 30 breakers span across 6 consecutive modbus registers as shown in
Table 2-37
HRGF Detection Operand States (6 items) on page 136
for memory locations.
Table 2-37 HRGF Detection status offsets
Bit
Value
0
Alarm Dropout
1
Alarm Pickup
2
Alarm Operated
Breaker Number
Register
Offset
Bit Offset
Notes
Breaker 1
0
0
Breaker 2
0
3
Breaker 3
0
6
Breaker 4
0
9
...
...
...
...
Advertising